What happens if the high frequency DC high voltage generator fails?

High-frequency DC high-voltage generator is suitable for DC high-voltage testing of zinc oxide surge arresters, magnetic discharge arresters, power cables, generators, transformers, switches and other equipment in the power sector, power departments of factories and mines, research institutes, railways, chemicals, and power plants. , is the best new generation of products in the new century.

Failure inspection and handling When the power switch is turned on, the digital display on the control box is off. Please check the power connection and all fuses. If the fuse is damaged, replace the new fuse with the amperage marked next to the fuse holder.

2. If the power switch is turned on, the digital display is on, the high-voltage display green light is off, and no high voltage is applied.

(1) Fault display The “Zero Return” light does not return to the zero position. Turn the high voltage output adjustment knob and the fine adjustment knob counterclockwise back to the zero position and turn the “Zero Return” indicator off.

(2) Fault display The “other” light is illuminated with two phenomena: ground protection, and disconnection protection.

a. The ground wire may not be connected properly, or the ground wire may not be reliably grounded. Please connect a reliable ground wire, turn off the power, and restart. b. It may be that the cable connecting the control box and the high voltage tower is not connected properly. After connecting the cable, turn off the power and restart it. This fault may occur when the welding heads at both ends of the cable are unsealed. Please solder the welding heads at both ends of the cable, turn off the power, and restart.

c. It is possible to disconnect the wire in one end of the control box. Please re-weld, turn off the power and restart.

3. Everything is OK, but it is protected in the process of not rising to the rated output voltage.

(1) Fault display "Overflow" light a. The test product is short circuited or the leakage current is too large. b. When the load is large, the voltage boost is too fast, the power is turned off, and the power is restarted, which slows down the boosting speed. (2) Fault display "Overvoltage" lamp over voltage protection setting knob is not at the maximum position, please rotate clockwise to the maximum position, turn off the power and restart.

4. When a short circuit occurs under high voltage of the test sample, all the fault indicator lights may be lit due to the large short-circuit current. This is normal, please restart the test product after troubleshooting.

5. After troubleshooting of the test sample, the fault indicator light is still on, and no high pressure can be applied. Power switch and fault protection reset switch, please turn off the power, restart, you can boost.

6. If the voltage fluctuation of the voltmeter is found to be too large, please check whether the shielded junction of the 7-pin connector of the two air plugs of the connecting cable is disconnected. If it is disconnected, please weld it well.

Microbend Mass Flow Meter

Sealand is a trustworthy manufacturer of Microbend Mass Flow Meter, Microbend Mass Flowmeter, Microbend Coriolis Mass Flow Meter, Microbend Coriolis Mass Flowmeter.

Site Selection for Mass Flow Meter Installation
a) Sensor stays away from mechanical vibration source, for example, pump. Use flexible pipe to connect meter with pipeline if inevitable. The housing of meter must be standalone, out of touch with any other device. There must be 3 times the size of sensor between 2 sensors if there are many flow meters on the same pipeline, to avoid resonance.
b) Do not install sensor on pipeline that easily expands with hot and contracts with cold, especially near expansion joint, which leads to a worse stability.
c) Sensor stays away from industrial electromagnetic field, such as large generator and transformer, better 5m at least. Such device influences the performance of drive coil and pickoffs. Make sure magnetic field intensity less than 400A/m.
d) Sensor shall be installed on lower pipeline, to be easily full of fluid.
e) Make sure Ex-mark meet application requirements if in hazardous area.
f) Build a sunshade if the meter is under direct solar radiation. g) Keep the meter from corrosive liquid.